Model: HMJ9001-Q
Product Overview:
The HMJ9001-Q Partial Discharge Detector is a multifunctional handheld device that utilizes five advanced detection methods—Transient Earth Voltage (TEV), Ultrasonic, High-Frequency Current (HFCT), and Ultra High Frequency (UHF)—to detect partial discharge (PD) conditions in various power equipment.
It is widely applicable to equipment such as switchgear, ring main units (RMU), GIS, power cables, transformers, and overhead lines.
- TEV sensors are used for switchgear and RMU detection.
- Airborne ultrasonic sensors are used for switchgear, RMU, and overhead lines.
- Contact ultrasonic sensors are used for transformers and GIS.
- HFCT sensors are used for transformers and cables.
- UHF sensors are used for transformers and GIS.
The instrument is compact, lightweight, easy to use, and highly efficient for field detection.
The HMJ9001-Q can connect with power grid PMS platforms via USB, Wi-Fi, or Bluetooth to download work orders and upload test data.
Key Features:
- 5-inch 800×480 touch screen display
- Communication interfaces: USB, Bluetooth, Wi-Fi, NFC
- Automatic partial discharge fault diagnosis
- Built-in library of typical PD pattern maps
- PRPD and PRPS pattern analysis supported
- Supports saving and playback of time-domain and pattern data
Core Functions:
- Integrates five types of sensors: TEV, airborne ultrasonic, contact ultrasonic, HFCT, and UHF
- Detects the frequency and intensity of TEV, ultrasonic, HFCT, and UHF PD signals
- Over-limit alarm function with red, yellow, and green indicators to show PD severity
- Ultrasonic detection uses external method, stereo pickup, and noise reduction to listen to discharge signals
- Playback and comparison of historical audio data
- PRPD and PRPS modes for discharge type identification
- Time-domain waveform detection mode for identifying typical discharge waveforms
- Storage and comparison of typical discharge pattern maps
- Equipped with data management software for comprehensive analysis and automatic report generation
Technical Specifications:
Parameter | Specification |
Time-domain waveform | 20ms raw time-domain waveform |
Spectrum display | PRPD and PRPS patterns, typical waveform integration |
Data storage | Supports time-domain and spectrum data saving and review |
Audio recording time | Adjustable from 10s to 120s |
Audio volume | 1–10 levels adjustable |
Operating system | Embedded Linux |
Communication | USB, Wi-Fi, Bluetooth, NFC |
Screen resolution | 800×480 |
Battery life | >8 hours |
Internal storage | 16GB |